The relay type NA11 can be used in radial networks as feeder or power transformer protection. In solidly grounded systems the residual overcurrent protection can be used on feeders of any lenght, while in ungrounded or Petersen coil and/or resistance grounded systems, the residual overcurrent protection can be used on feeders of small lenght in order to avoid unwanted trippings due to the capacitive current contribution of the feeder on external ground fault.
Beside to the phase and residual overcurrent protections, the automatic reclosing function is provided. The NA11 device may be shipped with traditional CTs or with low power (LPCT) current inputs.
FUNCTIONS
STANDARD PROTECTIVE & CONTROL ELEMENTS
Phase overcurrent side H and side L - 50/51
Maximum Residual Overcurrent - 50N/51N(1)
Automatic Recloser - 79
Breaker Failure - BF
CT Supervision - 74CT
Trip Circuit Supervision - 74TCS
Sequence of event Recorder (SER)
Sequence of Fault Recorder (SFR)
SW PACK OPTIONAL CONFIGURATION
Digital Fault Recorder (DFR)
HW PACK OPTIONAL CONFIGURATION
Thermal with Pt100 Probes - 26
COMMUNICATION FUNCTIONS
Modbus TCP-IP
One USB Type B local port for communication with ThyVisor setup software
Modbus protocol RTU RS485 / IEC 870-5-103 / DNP3
DOWNLOADS
Flyer NA11
NA11 Coding
Manual NA11
RELATED PRODUCTS
NA10
The relay type NA10 is typically used in radial HV, MV and LV networks as feeder or power transformer protection.
In solidly grounded systems the residual overcurrent protection can be used on feeders of any lenght, while in ungrounded or Petersen coil and/or resistance grounded systems, the residual overcurrent protection can be used on feeders of small lenght in order to avoid unwanted trippings due to the capacitive current contribution of the feeder on external ground fault.
The relay complies with CEI 0-16 requirements.
...
XMR-A
XMR-A is a part of XMORE platform, the complete range of IEDs for Medium Voltage application including feeder, motor, generator, transformer and capacitor bank.
Thanks to Hardware and Software modularity XMR-A is flexible and scalable in term of application and performance as:
Overcurrent and Earth fault protection (StandardSW configuration)