XMR-C

Capacitor bank protection

XMR-C is dedicated to the protection, measurement and supervision of capacitor banks and harmonic filters.
In addition, the relay has a series of protective functions that make it a multifunction relay.
Filter capacitor banks consist of capacitor bank and air core connected in series. Their task is to absorb the harmonic currents generated by loads and all above mentioned power electronic devices. The capacitor banks may be internally/externally fused or fuseless capacitor units.
The XMR-C relay provides protection of shunt capacitor banks and harmonic filter circuits with following configurations:
  • Single star grounded or ungrounded
  • Double star ungrounded or ungrounded
  • Delta
  • H configuration
The capacitor banks may be equipped with internally fused, externally fused or unfused capacitor units.
A suitable compensation method is provided by the protection relay to compensate the inherent unbalance neutral current
Protection 37, 49, 59H and 50(rms)/51(rms) are based on RMS measurement of the three phase currents (fundamental and harmonics up to the 50th).
Following input circuits are available:
  • Three phase current and one neutral current inputs with nominal currents independently selectable
  • at 1 A or 5 A by means of sw settings.
  • Three phase voltages (line-to-ground) with nominal voltages programmable in the range 50...130
  • V (UR=100V) and one residual voltage input with nominal voltage programmable in the range
  • 50...130 V (UER=100V).
In addition to the main protection element, the breaker failure (BF), CT monitoring (74CT), VT monitoring (74VT), Trip Circuit Supervision (TCS), and programmable logic (PLC) are also provided. Calibration, programming and readout modes of measurements and recordings are implemented through Personal Computer with Software support (ThyVisor) via communication bus. 


ACCURATE MEASUREMENTS

Enhancements to protect and analyze power system operation in disturbance conditions:

  • Up to 8 analogue inputs
  • Non conventional CT’s/VT’s inputs
  • 32 sample for cycle Oscillography fault recording
  • 64 sample for cycle measurement for accuracy of protection element
  • Up to 0,5 class Power and Energy measurement

COMMUNICATION SECURITY

Communication Security through redundancy protocol and Cyber Security package :

  • High available Seamless Redundancy support HSR
  • Parallel Redundancy Protocol support PRP
  • Rapid Spanning Tree Protocol RSTP
  • Advanced built in Cyber Security

TIME SYNCRONIZATION

Enhanced Time synchronization solution for SOE recording:

  • Precision Time Protocol PTP according to IEC1588
  • SNTP

NETWORK CONNECTIVITY

Widely implemented in Smart Grid and Substation Automation System:

  • IEC61850 Ed.1/Ed.2
  • IEC 870-5-103
  • Modbus (Serial/TCP)
  • DNP3 (Serial/TCP)


FUNCTIONS


STANDARD PROTECTIVE & CONTROL ELEMENTS

  • Under Voltage - 27
  • Under Current - 37
  • Negative sequence overcurrent - 46LT
  • Neutral unbalance current - 46N
  • Phase unbalance - 46U
  • Negative /positive sequence current ratio - I2/I1
  • Thermal Image Transformer - 49LT
  • Phase overcurrent side H and side L - 50/51
  • Calculated Residual Overcurrent - 50N/51N (Comp)
  • Overvoltage - 59
  • Residual Overvoltage - 59N
  • Negative sequence overvoltage - 59V2
  • 100% stator earth-fault - 27H - 59H
  • Ground directional overcurrent - 67N
  • Overfrequency - 81O
  • Underfrequency - 81U
  • Breaker Failure - BF
  • CT Supervision - 74CT
  • VT Supervision - 74VT
  • Trip Circuit Supervision - 74TCS
  • Remote TRIP
  • Second Harmonic Restraint
  • Multiple Profiles (A, B, C, D)
  • Highest harmonic distortion of the phase currents (THD-I)
  • Time Delay (TD)

SW PACK OPTIONAL CONFIGURATION

  • Thermal with Pt100 Probes - 26
HW PACK OPTIONAL CONFIGURATION
  • Arc flash

COMMUNICATION FUNCTIONS

  • Modbus TCP-IP
  • One Fibre Optic Ethernet port dedicated to IEC 61850
  • One USB Type B local port for communication with ThyVisor setup software
  • DNP3 TCP-IP
  • IEC60870-5-103
  • IEC61850 Ed.1 & Ed. 2

DOWNLOADS

Flyer XMR-C
User Manual XMR-C
Brochure XMORE
Additional modules XMore (XMRI - XMR16 - XMID32 - XMPT - XMCI)
Coding Sheet XMR-C

RELATED PRODUCTS

NC020

In recent years the harmonic producing part of total load has increased continuously because of the massive usage of power electronic in all the voltage levels. Thyristor convertors, frequency convertors, thyristor switches and static var compensator, such as thyristor controlled reactors (TCR) and thyristor switched capacitors (TSC), are commonly adopted in industrial applications and power utilities.
Filter capacitor banks consist of capacitor bank and series connected air core. Their task is to absorb the harmonic currents generated by loads and all above mentioned power electronic devices.
The aim of NC020 is to provide a reliable and cost effective solution for such an application granting capacitor bank safe operations.

...

NC20

The relay type NC20 provides protection of shunt capacitor banks and harmonic filter circuits. The capacitor banks may have the following configurations:

  • Single Wye grounded.
  • Single Wye ungrounded (with a resistor on the output of the neutral unbalance voltage transformer in order to develop the appropriate input current for the unbalance protection).
  • Double Wye ungrounded.
The capacitor banks may be: internally/externally fused or fuseless capacitor units. A suitable compensation method is provided to compensate the inherent unbalance neutral current
Protections 37, 49 and 50/51 (RMS) are based on RMS value measurement of the three phase currents (fundamental and harmonics up to the 11th)

...