NC20

Capacitor bank protection

The relay type NC20 provides protection of shunt capacitor banks and harmonic filter circuits. The capacitor banks may have the following configurations:

  • Single Wye grounded.
  • Single Wye ungrounded (with a resistor on the output of the neutral unbalance voltage transformer in order to develop the appropriate input current for the unbalance protection).
  • Double Wye ungrounded.
The capacitor banks may be: internally/externally fused or fuseless capacitor units. A suitable compensation method is provided to compensate the inherent unbalance neutral current
Protections 37, 49 and 50/51 (RMS) are based on RMS value measurement of the three phase currents (fundamental and harmonics up to the 11th)


FUNCTIONS


STANDARD PROTECTIVE & CONTROL ELEMENTS

  • Under Voltage - 27
  • Under Current - 37
  • Negative sequence overcurrent - 46LT
  • Phase overcurrent side H and side L - 50/51
  • Maximum Residual Overcurrent - 50N/51N(1)
  • Overvoltage - 59
  • Breaker Failure - BF
  • CT Supervision - 74CT
  • Trip Circuit Supervision - 74TCS
  • Neutral unbalance current - 46N
  • Second Harmonic Restraint
  • Sequence of Fault Recorder (SFR)
  • Sequence of event Recorder (SER)

SW PACK OPTIONAL CONFIGURATION

  • Digital Fault Recorder (DFR)
HW PACK OPTIONAL CONFIGURATION
  • Thermal with Pt100 Probes - 26

COMMUNICATION FUNCTIONS

  • One USB Type B local port for communication with ThyVisor setup software

DOWNLOADS

NC20 Manual
Flyer NC20
NC20 Coding
PRO-N NC20 IEC 61850 Certificate

RELATED PRODUCTS

NC020

In recent years the harmonic producing part of total load has increased continuously because of the massive usage of power electronic in all the voltage levels. Thyristor convertors, frequency convertors, thyristor switches and static var compensator, such as thyristor controlled reactors (TCR) and thyristor switched capacitors (TSC), are commonly adopted in industrial applications and power utilities.