XMR-D

XMR-D Protection Relay for Generators


The XMR-D is part of the XMORE platform, a comprehensive range of IEDs for medium voltage applications that includes power supplies, motors, generators, transformers, and capacitor banks. The Thytronic IED XMR-D is a complete multifunctional relay for the protection of motors and generators, including the differential element. Thanks to its hardware and software modularity, the XMR-D is flexible and scalable in terms of applications and performance.

Features of the XMR-D Protection Relay for Generators


Equipped with a wide range of standard features, the XMR-D relay for generator protection provides complete protection through the supervision and control of crucial parameters such as maximum phase current, frequency, residual voltage, and many other variables essential for the proper functioning of the generator. This relay also integrates an advanced communication security system, utilizing redundancy protocols and built-in cybersecurity to ensure high reliability and data protection. Moreover, with an advanced time synchronization solution, it allows accurate recording of event sequences (SOE).

Network connectivity includes various implementations of protocols widely used in Smart Grids and substations, making it compatible with multiple environments and automation systems. The protection and control functionalities are extremely detailed and include various measures, such as maximum directional active power, trip circuit supervision, and many others, providing complete and customized protection for the generator. Additional hardware and software configuration options offer further levels of control and customization, including thermal functions through Pt100 thermal probes, the Arc Flash function, and other optional elements to enhance the safety and efficiency of the system.

ACCURATE MEASUREMENTS

Enhancements to protect and analyze power system operation in disturbance conditions:

  • Up to 12 analogue inputs
  • 32 sample for cycle Oscillography fault recording
  • 64 sample for cycle measurement for accuracy of protection element
  • Up to 0,5 class Power and Energy measurement

TIME SYNCRONIZATION

Enhanced Time synchronization solution for SOE recording:

  • Precision Time Protocol PTP according to IEC1588
  • SNTP

COMMUNICATION SECURITY

Communication Security through redundancy protocol and Cyber Security package :

  • High available Seamless Redundancy support HSR
  • Parallel Redundancy Protocol support PRP
  • Rapid Spanning Tree Protocol RSTP
  • Advanced built in Cyber Security

NETWORK CONNECTIVITY

Widely implemented in Smart Grid and Substation Automation System:

  • IEC61850 Ed.1/Ed.2
  • IEC 870-5-103
  • Modbus (Serial/TCP)
  • DNP3 (Serial/TCP)


FUNCTIONS


STANDARD PROTECTIVE & CONTROL ELEMENTS

  • Unintentional energisation at standstill protection - 50/27
  • Calculated Residual Overcurrent - 50N/51N (Comp)
  • Phase rotation direction check - 47
  • Positive Sequence Undervoltage - 27V1
  • Phase overcurrent side H and side L - 50/51
  • Overfrequency - 81O
  • Underfrequency - 81U
  • Residual Overvoltage - 59N
  • VT Supervision - 74VT
  • SynchroCheck - 25
  • Remote TRIP
  • Voltage-controlled / restraint overcurrent - 51V
  • Second Harmonic Restraint
  • Negative sequence overcurrent - 46LT
  • Ground directional overcurrent - 67N
  • Directional earth fault overcurrent - 67N(Comp)
  • Double slope biased differential for Generator/ Motor/Transformer -87M-87G-87T
  • Overvoltage - 59
  • CT Supervision - 74CT
  • Under Voltage - 27
  • Directional reactive overpower -32Q
  • Directional active underpower - 37P
  • Directional reactive underpower - 37Q
  • Out of Step Protection - 78
  • Directional active overpower - 32P
  • Maximum number of startings (Restart inhibition) - 66
  • Low impedance restricted earth fault - 64REF
  • Under Current - 37
  • Frequency rate of change - 81R
  • Breaker Failure - BF
  • Negative sequence overvoltage - 59V2
  • Loss of Field - 40
  • Automatic Recloser - 79
  • Maximum Residual Overcurrent - 50N/51N(1)
  • Negative /positive sequence current ratio - I2/I1
  • Thermal Image Motor/Generator - 49MG
  • Under Impedence - 21
  • Minimum Power Factor - 55
  • Trip Circuit Supervision - 74TCS
  • Overexicitation - 24
  • Maximum Residual Overcurrent - 50N/51N(2)
  • Negative sequence overcurrent Motor/Generator - 46MG
  • Vector Jump - DPHI
  • Locked Rotor - 51LR(48)/14
  • Directional Phase Overcurrent - 67
  • 100% stator earth-fault - 27H - 59H
  • Thermal Image Transformer - 49LT
  • Multiple Profiles (A, B)
HW PACK OPTIONAL CONFIGURATION
  • Thermal with Pt100 Probes - 26
  • Arc flash
  • Rotor Earth Fault - 64F